home *** CD-ROM | disk | FTP | other *** search
/ PC Electronic Plus / PC Electronics Plus (Most Significant Bits)(1995).ISO / pma / btest6.gif < prev    next >
Graphics Interchange Format  |  1994-09-08  |  15KB  |  640x480  |  4-bit (5 colors)
Labels: text | electronics | screenshot | display | software | font | number | web page | website
OCR: BURGER Thermally Test Your Tower When the data collection and analysis is complete, the performance test results are reported as illustrated by the sample results sheet shown below CTI TEST INTERPRETATION ( Sample Test Analysis Printout Sheet ) Mechanical, induced draft cooling tower Tower capability determined by CTI characteristic method As per CTI Code ATC-105, February 1990, paragraph II-A-(a) THERMAL TEST 13 AUGUST 1992 LAMBERT AIRPORT COOLING TOWER CS-576-60 INPUT DATA: DESIGN TEST RESULTS Water flows .. .US GPM 3750.0 3389.10 Kall/L at design point. 1.407 Wet bulb temperature ... ... F 78.0 64.30 Air temp at fan (design) .. 90.31 Cold water temperature ...... 85.0 71.60 Air density at fan (design) .lb/ft 3 0.0707 Hot water temperature. .... F 95.0 78.30 Air temp at fan (test) .. 75. ...